ASDA-M Chapter 8 Parameters
Revision December, 2014 8-125
P3-11 CANOP CANopen Selection
Address: 0316H
0317H
Parameter
Attribute
Parameter for three axes
Related Section: -
Operationa
l Interface
Panel / Software Communication
Default
0x0000
Control
Mode
CANopen
Unit
-
Range
Shown as below
Data Size
16bit
Format
HEX
Settings
Synchronous setting of CANopen is divided into X, Y, Z and U
(hexadecimal):
Item U Z Y X
Functio
n
undefine
d
undefined
undefine
d
Whether the
parameter is saved
into EEPROM
Range - - - 0 ~ 1
The definition is as follows:
X=1: When writing parameters via PDO, parameters will be
saved in EEPROM.
X=0: When writing parameters via PDO, parameters will not be
saved in EEPROM.
Y: undefined
Z: undefined
U: undefined
NOTE
This parameter is effective in the model of ASDA-M-M/F.
If X is set to 1 and write parameters by PDO continuously, it will
shorten the lifetime of EEPROM.

Table of Contents

Other manuals for Delta ASDA-M Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASDA-M Series and is the answer not in the manual?

Delta ASDA-M Series Specifications

General IconGeneral
BrandDelta
ModelASDA-M Series
CategoryServo Drives
LanguageEnglish

Related product manuals