Chapter 7 Optional AccessoriesME300
File type
mismatch
(ERR8)
File type mismatch
Data to be copied are not the correct type, so
the setting cannot be changed.
1. Check if the products’ serial numbers to be
copied are in the same category. If they are
in the same category, try to copy the setting
again.
If this solution does not work, contact your
authorized dealer for assistance.
Password locked
(ERR9)
File is locked with
password
A setting cannot be changed because some
data are locked.
1. Check if the data are unlocked or able to be
unlocked. If the data are unlocked, try to
change the setting again.
2. Shut down the system, wait for ten minutes,
and then restart the system.
If none of the above solutions works, contact
your local authorized dealer for assistance.
Password fail
(ERR10)
File password
failure
A setting cannot be changed because the
password is incorrect.
1. Check if the password is correct. If the
password is correct, try to change the
setting again.
2. Shut down the system, wait for ten minutes,
and then restart the system.
If none of the above solutions works, contact
your local authorized dealer for assistance
Version fail
(ERR11)
File version
mismatch
A setting cannot be changed because the
version of the data is incorrect.
1. Check if the version of the data matches
motor drive. If it matches, try to change the
setting again.
If this solution does not work, contact your
local authorized dealer for assistance.
VFD Time out
(ERR12)
AC drive copy
function time-out
A setting cannot be changed because the data
copying time-out expired.
1. Try copying the data again.
2. Check if copying data is authorized. If it is
authorized, try to copy the data again.
3. Shut down the system, wait for ten minutes,
and then restart the system.
If none of the above solutions works, contact
your local authorized dealer for assistance.
※ The content in this chapter only applies to KPC-CC01 keypad V1.01 and later version(s).