Chapter 11 Summary of Parameter SettingsME300
11-15
Pr. Explanation Settings Default
02-25
The width of the desired
frequency reached 2
0.00–599.00 Hz 2.00
02-34
Output frequency setting for
multi-function output
terminal
0.00–599.00 Hz 0.00
02-35
External operation control
selection after reset and
reboot
0: Disable
1: Drive runs if the RUN command remains after reset
or reboot.
0
02-47 Motor zero-speed level 0–65535 rpm 0
02-50
Display the status of multi-
function input terminal
Monitor the status of multi-function input terminals
Read
only
02-51
Display the status of multi-
function output terminal
Monitor the status of multi-function output terminals
Read
only
02-54
Display the frequency
command executed by
external terminal
0.00–599.00 Hz (Read only)
Read
only
02-58
Multi-function output
terminal (function 42): brake
frequency check point
0.00–599.00 Hz 0.00
02-72
Preheating output current
level
0–100% 0
02-73 Preheating output cycle 0–100% 0
02-81
EF active when terminal
count value reached
0: Terminal count value reached, no EF displays
(continue operation)
1: Terminal count value reached, EF is active
0
02-82
Initial Frequency command
(F) mode after stop
0: Use current Frequency command
1: Use zero Frequency command
2: Refer to Pr.02-83 to setup
0
02-83
Initial Frequency command
(F) setting after stop
0.00–599.0 Hz 60.00