Chapter 11 Summary of Parameter SettingsME300
11-21
Pr. Explanation Settings Default
05-17
No-load current for
induction motor 2 (A)
0.00–Pr.05-13 default
Depending
on the
model
power
05-18
Stator resistance (Rs) for
induction motor 2
0.000–65.535 Ω
Depending
on the
model
power
05-19
Rotor resistance (Rr) for
induction motor 2
0.000–65.535 Ω
0.000
05-20
Magnetizing inductance
(Lm) for induction motor 2
0.0–6553.5 mH 0.0
05-21
Stator inductance (Lx)
for induction motor 2
0.0–6553.5 mH 0.0
05-22
Multi-motor (induction)
selection
1: Motor 1
2: Motor 2
1
05-23
Frequency for
Y-connection / -connection
switch for an induction
motor
0.00–599.00 Hz
60.00
05-24
Y-connection / -connection
switch for an induction
motor
0: Disable
1: Enable
0
05-25
Delay time for
Y-connection / -connection
switch for an induction
motor
0.000–60.000 sec.
0.200
05-26
Accumulated Watt-second
for a Motor in Low Word
(W-msec.)
Read only 0.0
05-27
Accumulated Watt-second
for a Motor in High Word
(W-sec.)
Read only 0.0
05-28
Accumulated Watt-hour for
a motor (W-hour)
Read only 0.0
05-29
Accumulated Watt-hour for
a motor in low word (kW-
hour)
Read only 0.0
05-30
Accumulated Watt-hour for
a motor in high word (MW-
hour)
Read only 0.0
05-31
Accumulated motor
operation time (minutes)
0–1439 min. 0