Chapter 11 Summary of Parameter SettingsME300
11-26
Pr. Explanation Settings Default
06-27
Electronic thermal relay
selection 2 (motor 2)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
2
06-28
Electronic thermal relay
action time 2 (motor 2)
30.0–600.0 sec.
60.0
06-29 PTC detection selection
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
0
06-30 PTC level 0.0–100.0%
50.0
06-31
Frequency command for
malfunction
0.00–599.00 Hz Read only
06-32
Output frequency at
malfunction
0.00–599.00 Hz Read only
06-33
Output voltage at
malfunction
0.0–6553.5 V Read only
06-34
DC bus voltage at
malfunction
0.0–6553.5 V Read only
06-35
Output current at
malfunction
0.00–655.35 Amp Read only
06-36
IGBT temperature at
malfunction
-3276.7–3276.7
o
C Read only
06-38
Motor speed at
malfunction
-32767–32767 rpm Read only
06-40
Status of the multi-
function input terminal at
malfunction
0000h–FFFFh Read only
06-41
Status of the multi-
function output terminal at
malfunction
0000h–FFFFh Read only
06-42
Drive status at
malfunction
0000h–FFFFh Read only
06-44
STO latch selection
(only for models built-in
with STO function)
0: STO Latch
1: STO No Latch
0
06-45
Output phase loss
detection action (OPHL)
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
3