Chapter 11 Summary of Parameter SettingsME300
11-28
Pr. Explanation Settings Default
06-69
Operation time of fault
record 4 (Days)
0–65535 days Read only
06-70
Operation time of fault
record 4 (Minutes)
0–1439 min. Read only
06-71 Low current setting level 0.0–100.0% 0.0
06-72
Low current detection
time
0.00–360.00 sec. 0.00
06-73 Low current action
0 : No function
1 : Fault and coast to stop
2 : Fault and ramp to stop by the second deceleration
time
3 : Warn and continue operation
0
06-80 Fire mode
0: Disable
1: Forward (counterclockwise) operation
2: Reverse (clockwise) operation
0
06-81
Operating frequency
when running fire mode
0.0 – 599.00 Hz 60.00
06-88
Operation times when
running fire mode
0–65535 times Read only
06-90
Operation time of fault
record 5 (Day)
0–65535 days Read only
06-91
Operation time of fault
record 5 (Min.)
0–1439 min. Read only
06-92
Operation time of fault
record 6 (Day)
0–65535 days Read only
06-93
Operation time of fault
record 6 (Min.)
0–1439 min. Read only