Chapter 11 Summary of Parameter SettingsME300
11-29
07 Special Parameters
Pr. Explanation Settings Default
07-00
Software brake chopper
action level
115V / 230V models: 350.0–450.0 V
DC
460V models: 700.0–900.0 V
DC
370.0
740.0
07-01 DC brake current level 0–100%
0
07-02 DC brake time at start-up 0.0–60.0 sec.
0.0
07-03 DC brake time at STOP 0.0–60.0 sec.
0.0
07-04
DC brake frequency at
STOP
0.00–599.00 Hz
0.00
07-05 Voltage increasing gain 1–200% 100
07-06
Restart after momentary
power loss
0: Stop operation
1: Speed tracking by the speed before the power loss
2: Speed tracking by the minimum output frequency
0
07-07
Allowed power loss
duration
0.0–20.0 sec.
2.0
07-08 Base Block time 0.0–60.0 sec.
0.5
07-09
Current limit of speed
tracking
20–200%
100
07-10 Restart after fault action
0: Stop operation
1: Speed tracking by current speed
2: Speed tracking by minimum output frequency
0
07-11
Number of times of
restart after fault
0–10
0
07-12
Speed tracking during
start-up
0: Disable
1: Speed tracking by the maximum output frequency
2: Speed tracking by the motor frequency at start
3: Speed tracking by the minimum output frequency
0
07-13 dEb function selection
0: Disable
1: dEb with auto-acceleration / auto-deceleration, the
drive does not output the frequency after the power
is restored.
2: dEb with auto-acceleration / auto-deceleration, the
drive outputs the frequency after the power is
restored.
0
07-15 Dwell time at acceleration 0.00–600.00 sec.
0.00
07-16
Dwell frequency at
acceleration
0.00–599.00 Hz
0.00
07-17
Dwell time at
deceleration
0.00–600.00 sec.
0.00
07-18 Dwell frequency at 0.00–599.00 Hz
0.00