Chapter 11 Summary of Parameter SettingsME300
11-30
Pr. Explanation Settings Default
deceleration
07-19 Fan cooling control
0: Fan is always ON
1: Fan is OFF after the AC motor drive stops for one
minute.
2: Fan is ON when the AC motor drive runs, fan is
OFF when the AC motor drive stops.
3: Fan turns ON when IGBT temperature reaches
around 60
o
C.
5: Fan turns ON/OFF when the AC motor drive
runs/stops and stays in Stand By mode at zero
speed.
3
07-20
Emergency stop (EF) &
force to stop selection
0: Coast to stop
1: Stop by the first deceleration time
2: Stop by the second deceleration time
3: Stop by the third deceleration time
4: Stop by the fourth deceleration time
5: System deceleration
6: Automatic deceleration
0
07-21
Automatic energy-saving
selection
0: Disable
1: Enable
0
07-23
Automatic voltage
regulation (AVR) function
0: Enable AVR
1: Disable AVR
2: Disable AVR during deceleration
0
07-24
Torque command
filter time
(V/F and SVC control mode)
0.001–10.000 sec. 0.050
07-25
Slip compensation
filter time
(V/F and SVC control mode)
0.001–10.000 sec. 0.100
07-26
Torque compensation
gain
IM: 0–10 (when Pr.05-33 = 0)
PM: 0–5000 (when Pr.05-33 = 1 or 2)
1
07-27 Slip compensation gain 0.00–10.00
0.00
(Default value
is 1.00 in
SVC mode)
07-29 Slip deviation level
0.0–100.0%
0: No detection
0
07-30
Over-slip deviation
detection time
0.0–10.0 sec.
1.0