Chapter 11 Summary of Parameter SettingsME300
11-31
Pr. Explanation Settings Default
07-31
Over-slip deviation
treatment
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
0
07-32
Motor oscillation
compensation factor
0–10000
1000
07-33
Auto-restart interval of
fault
0.0–6000.0 sec.
60.0
07-38
PMSVC voltage feed
forward gain
0.50–2.00 1.00
07-62 dEb gain (Kp) 0–65535 8000
07-63 dEb gain (Ki) 0–65535 150
07-71
Torque compensation
gain
(motor 2)
IM: 0–10 (when Pr.05-33 = 0)
PM: 0–5000 (when Pr.05-33 = 1 or 2)
1
07-72
Slip compensation gain
(motor 2)
0.00–10.00
0.00
(Default value
is 1 in SVC
mode)