Chapter 12 Description of Parameter Settings
ME300
12.1-02-23
The figure below shows the timing relationship between preheating function and enabling DC
brake.
02-81
EF Active when the Terminal Count Value Reached
Default: 0
Settings 0: Terminal count value reached, no EF displays (continues operate).
1: Terminal count value reached, EF is active.
02-82
Initial Frequency Command (F) Mode after Stop
Default: 0
Settings 0: Use current Frequency command
1: Use zero Frequency command
2: Refer to Pr.02-83 to set up
02-83
Initial Frequency Command (F) Setting after Stop
Default: 60.00
Settings 0.00599.0 Hz