Chapter 12 Description of Parameter SettingsME300
12.1-03-17
03-45
AI Level 1 (upper limit)
Default: 50
Settings -100100%
03-46
AI Level 2 (lower limit)
Default: 10
Settings -100100%
Multi-function output terminal 67 must work with Pr.03-44 to select input channels. When analog
input level is higher than Pr.03-45, multi-function output acts; when analog input level is lower than
Pr.03-46, multi-function output terminals stop outputting.
When setting levels, AI upper level must be higher than AI lower level.
03-50
Analog Input Curve Selection
Default: 0
Settings 0: Normal Curve
1: Three-point curve of AVI (& AI10)
2: Three-point curve of ACI (& AI11)
03-57
ACI Lowest Point
Default: 4.00
Settings Pr.03-28 = 1, 0.0010.00 mA
Pr.03-28 ≠ 1, 0.0020.00 mA
03-58
ACI Proportional Lowest Point
Default: 0.00
Settings 0.00100.00%
03-59
ACI Mid-point
Default: 12.00
Settings Pr.03-28 = 1, 0.0010.00 mA
Pr.03-28 ≠ 1, 0.0020.00 mA
03-60
ACI Proportional Mid-point
Default: 50.00
Settings 0.00100.00%
03-61
ACI Highest Point
Default: 20.00
Settings Pr.03-28 = 1, 0.0010.00 mA
Pr.03-28 ≠ 1, 0.0020.00 mA
03-62
ACI Proportional Highest Point
Default: 100.00
Settings Pr.03-28 ≠ 1,
0.00100.00%
When Pr.03-28 ≠ 1, the ACI setting is 0–20 mA or 4–20 mA and the unit is current (mA).
When you set the analog input ACI to the Frequency command, 100% corresponds to Fmax
(Pr.01-00 Maximum Operation Frequency).
The output % becomes 0% when the ACI input value is lower than lowest point setting.
For example: