Chapter 12 Description of Parameter Settings
ME300
12.1-06-23
06-71
Low Current Setting Level
Default: 0.0
Settings 0.0100.0%
06-72
Low Current Detection Time
Default: 0.00
Settings
0.00360.00 sec.
06-73
Low Current Action
Default: 0
Settings 0 : No function
1 : Fault and coast to stop
2 : Fault and ramp to stop by the second deceleration time
3 : Warn and continue operation
The drive operates according to the setting for Pr.06-73 when the output current is lower than the
setting for Pr.06-71 and when the time of the low current exceeds the detection time for Pr.06-72.
Use this parameter with the external multi-function output terminal 44 (for low current output).
The low current detection function does not execute when drive is in sleep or standby status.
06-80
Fire Mode
Default: 0
Settings
0: Disable
1: Forward (counterclockwise) operation
2: Reverse (clockwise) operation
Use this parameter with multi-function input terminal setting 58 or 59, and multi-function output
terminal setting 53.
0: Fire detection is invalid.
1: The motor operates in a counterclockwise direction (U, V, W).
2: The motor operates in a clockwise direction (U, W, V).
06-81
Operating Frequency in Fire Mode
Default: 60.00
Settings 0.00599.00 Hz
06-88
Operation Times in Fire Mode
Default: Read only
Settings 0–65535 times