Chapter 12 Description of Parameter Settings
ME300
12.1-08-15
08-75
PID2 parameter switch condition
Default: 0
Settings 0: No switching (refer to Pr.08-01Pr.08-03)
1: Auto-switch based on the output frequency
2: Auto-switch based on the deviation
08-76
PID2 parameter switch deviation 1
Default: 10.00
Settings 0.00Pr.08-77%
08-77
PID2 parameter switch deviation 2
Default: 40.00
Settings Pr.08-76100.00%
A set of PID parameters cannot meet the requirements of the entire running process in some
applications. Use Pr.08-75 to switch to the second group of PID parameter Pr.08-31Pr.08-33.
The setting method for Pr.08-3108-33 is the same as that for Pr.08-0108-03.
The two sets of PID parameters switch automatically according to the frequency and deviation.
Switch according to the output frequency:
When the output frequency is between Pr.01-07 and Pr.01-00, the PID parameter is the
linear interpolation value between the two PID parameter groups.
Switch according to the deviation:
When the deviation absolute value between the set point and feedback is smaller than
Pr.08-76 (PID2 Parameter Switch Deviation 1), the first group PID parameters are used.
When the deviation absolute value between the set point and feedback is larger than Pr.08-
77 (PID2 Parameter Switch Deviation 2), the second group PID parameters are used.