Chapter 12 Description of Parameter Settings
ME300
When the deviation absolute value between the set point and feedback is between Pr.08-
76 and Pr.08-77, the PID parameter is the linear interpolation value between the two PID
parameter groups.
Allowed reverse running time after start-up
Default: 0.0
Settings 0.0–6553.5 sec.
When Pr.08-78 is not set to 0, allowed reverse running time after start-up is enabled.
When it set to 1
second, the PID control is not allowed to change the running direction within 0–1
seconds of starting time (Pr.08-21 = 0), and is allowed to change after 1 second of starting time
(Pr.08-21 = 1).