Chapter 12 Description of Parameter Settings
ME300
12.1-09-13
Example:
ASCII mode RTU mode:
Address
Function
Exception code
LRC CHK
END
The explanation of error codes
Error code Explanation
Function code is not supported or unrecognized.
Address is not supported or unrecognized.
Data is not correct or unrecognized.
Failure to execute this function code
Communication Response Delay Time
Default: 2.0
Settings 0.0–200.0 ms
Sets the response delay time after the AC motor drive receives a communication command as
shown in the following.
PC or PLC command
Handling time
of the AC drive
Response Delay Time
Pr.09-09
Response Message
of the AC Drive
RS-485 BUS
Communication Main Frequency
Default: 60.00
Settings 0.00–599.00 Hz
When you set Pr.00-20 to 1 (RS-485 serial communication), the AC motor drive saves the last
Frequency command into Pr.09-10 when there is abnormal power off or momentary power loss.
After the drive reboots when power is restored, it checks the frequency in Pr.09-10 if no new
Frequency command is input. When a Frequency command of 485 changes (the Frequency
command source must be set as Modbus), this parameter also changes.