Chapter 12 Description of Parameter Settings
ME300
Selection of Pump Start-up Sequence
Default: 1
Settings 0: By pump’s ID #
1: By the running time.
0: By pump ID#, (1 2 3 4 1)
1: By the shortest running time
Running Time of Multi-pump under Alternative Operation
Default: 60.0
Settings 0.0–360.0 sec.
This parameter only applies for the master pump.
The assigned value (setting value) of time to switch between master pump and slave pump.
Simple Positioning Stop Frequency 0
Default: 0.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 1
Default: 5.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 2
Default: 10.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 3
Default: 20.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 4
Default: 30.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 5
Default: 40.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 6
Default: 50.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 7
Default: 60.00
Settings 0.00–599.00 Hz
The settings for Pr.12-20–Pr.12-27 must meet the following condition:
Pr.12-20 ≤ Pr.12-21 ≤ Pr.12-22 ≤ Pr.12-23 ≤ Pr.12-24 ≤ Pr.12-25 ≤ Pr.12-26 ≤ Pr.12-27.
If any two of the parameters (between Pr.012-20–Pr.12-27) have the same stop frequency, their
Delay Time of Simple Positioning Stop must be the same as well.