Chapter 12 Description of Parameter Settings
ME300
Group setting 05: Conveyor
The following table lists the relevant conveyor setting application parameters.
Pr. Explanation Settings
00-11 Speed control mode 0 (VF)
00-16 Load selection 0 (Normal load)
00-20
Master frequency command source
(AUTO, REMOTE)
2 (External analog input)
00-21 Operation command source (AUTO, REMOTE) 1 (External terminals)
01-00 Motor 1 maximum operation frequency Default setting
01-01 Output rated / base frequency of motor 1 Default setting
01-02 Output rated / base voltage of motor 1 Default setting
01-03 Mid-point frequency 1 of motor 1 Default setting
01-04 Mid-point voltage 1 of motor 1 Default setting
01-05 Mid-point frequency 2 of motor 1 Default setting
01-06 Mid-point voltage 2 of motor 1 Default setting
01-07 Minimum output frequency of motor 1 Default setting
01-08 Minimum output voltage of motor 1 Default setting
01-12 Acceleration time 1 10.00 (sec.)
01-13 Deceleration time 1 10 (sec.)
Group setting 07: Packing
The following table lists the relevant packing setting application parameters.
Pr. Explanation Settings
00-11 Speed control mode 0 (VF)
00-20
Master frequency command source
(AUTO, REMOTE)
0 (Digital keypad)
00-21 Operation command source (AUTO, REMOTE) 2 (RS-485 Communication input)
02-00 Two-wire / Three-wire operation control
1 (two-wire mode 1, power on for
operation control (M1: FWD /
STOP, M2: REV / STOP))
01-00 Motor 1 maximum operation frequency Default setting
01-01 Output rated / base frequency of motor 1 Default setting
01-02 Output rated / base voltage of motor 1 Default setting
01-03 Mid-point frequency 1 of motor 1 Default setting
01-04 Mid-point voltage 1 of motor 1 Default setting
01-05 Mid-point frequency 2 of motor 1 Default setting
01-06 Mid-point voltage 2 of motor 1 Default setting
01-07 Minimum output frequency of motor 1 Default setting
01-08 Minimum output voltage of motor 1 Default setting
01-12 Acceleration time 1 10.00 (sec.)
01-13 Deceleration time 1 10 (sec.)