Chapter 14 Fault Codes and Descriptions
ME300
14-50
No. Display on LED Keypad Fault Name Fault Descriptions
157
Pump PID
feedback error (dEv)
Pump PID feedback error
Action and Reset
Action condition Feedback value < target value × (1 - Pr.08-13)
Action time Pr.08-14
Fault treatment parameter Pr.08-62
Reset method Self-recovery or manual reset
Reset condition
Set as Warm: Feedback value target value (1 - Pr.08-13) automatic recovery
Set as Fault
: Immediately reset
Record Error will be recorded
Cause Corrective Actions
Unreasonable parameter settings Pr.08-14
Time extension
Motor error Check if the motor works normally.