Chapter 6 Control TerminalsME300
Terminals Terminal Function Description
AFM
Multi-function analog
voltage output
Switch: The AFM default is 0–10 V (voltage mode).
Voltage mode
Range: 0–10 V corresponding to the maximum operating range of
the control object
Max. output current: 2 mA. Max. Load: 5 kΩ
AFM resolution = 12 bits
ACM Analog Signal Common Common for analog terminals
PE RS-485
PE terminal is for shielded cable to grounding to decrease the
interference when you use RS485 communication.
RJ45
PIN 1, 2, 6: Reserved PIN 3, 7: GND2 PIN 4: SG-
PIN 5: SG+ PIN 8: D+10 V (provide KPC-CC01 power supply)
* Analog control signal wiring specification: 0.82 mm
2
[18 AWG] with shielded stranded wire.