Chapter 6 Control TerminalsME300
6-5
Terminals Terminal Function Description
RA
Multi-function output
(Relay N.O. a)
Resistive Load
3 A (N.O.)/3 A (N.C.) 250 V
AC
5 A (N.O.)/3 A (N.C.) 30 V
DC
Inductive Load (COS = 0.4)
1.2 A (N.O.)/1.2 A (N.C.) 250 V
AC
2.0 A (N.O.)/1.2 A (N.C.) 30 V
DC
Various kinds of monitor signals output, e.g.: operation, frequency
reached, overload indication etc.
RB
Multi-function output
(Relay N.C. b)
RC
Multi-function output
common (Relay)
+10 V
DC
Potentiometer
power supply
+10.5 ± 0.5 V
DC
/ 20 mA
AI Analog input
The AVI terminal default voltage mode is set to 010 V. To use the
current mode, the AVI must be switched to the current mode position
(0–20 mA / 4–20 mA), as the red frame below shows, and then set
Pr.03-28.
Voltage (AVI) mode
Impedance: 20 kΩ
Range: 0–10 V = 0–Max. Output Frequency (Pr.01-00)
Range switching according to Pr.03-00, Pr.03-28.
AVI resolution = 12 bits
Current (ACI) mode
Impedance: 250 Ω
Range: 020 mA / 4–20 mA = 0–Max. Output Frequency (Pr.01-00)
Range switching according to Pr.03-28.
ACI resolution = 12 bits