EasyManuals Logo

Distech Controls EC-BOS-9 User Manual

Distech Controls EC-BOS-9
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
Chapter 2 Commissioning EC-BOS-9 Install and Startup Guide
Notice that in the Nav tree, the platform instance for that EC-BOS is now dimmed.
Step 5 Assuming that you changed the EC-BOS’s IP address during commissioning, right-click and close
that platform instance, as this would make that connection instance invalid.
Step 6 Do one of the following:
If you did not change its IP address, after several minutes you should be able to double-click the
platform instance again to reconnect.
Open a platform connection using the controller’s new (changed) IP address.
Going forward, you must access the controller by its new (assigned) IP address. EC-Net 4 Pro keeps
a history of TCP/IP changes made.
Use the credentials for the new platform user you created to replace the factory-default platform user,
or if you created additional platform users, log in with the credentials you created for one of them.
Step 7 If you changed your PC’s IP address to commission the controller, be sure to reconfigure your PC’s
TCP/IP settings back to appropriate settings to communicate with it. Otherwise, you will be unable to
connect to the PC to commission another controller.
30 August 14, 2023

Other manuals for Distech Controls EC-BOS-9

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Distech Controls EC-BOS-9 and is the answer not in the manual?

Distech Controls EC-BOS-9 Specifications

General IconGeneral
BrandDistech Controls
ModelEC-BOS-9
CategoryController
LanguageEnglish

Related product manuals