Chapter 5 Troubleshooting EC-BOS-9 Install and Startup Guide
The included decoded modTime value is easier to read. For example, 13-Jan-2024 03:36 PM EST
instead of d20150113153640).
Under each folder are two properties:
• priorValue reports the TCP/IP settings that existed before the change.
• newValue reports the TCP/IP settings that existed after the change.
Step 3 Expand a priorValue or newValue to see the reported settings.
Restoring factory defaults (EC-BOS-9)
The process of recovering factory defaults deletes all platform and station data, and returns the controller to the
state it was in when it shipped from the factory. If you cannot commission the controller because you made an
error when entering the default platform daemon credentials or passphrase, you can restore factory defaults
and start again. Also, when decommissioning a controller, a best practice is to recover the factory defaults,
which removes the platform and station data from the controller. This procedure uses a terminal emulator pro-
gram to access the controller’s system shell menu.
Prerequisites:
• You have administrator-level platform credentials.
• You have backed up all data from the controller.
• If you are planning a “power—on” reboot using the serial shell menu
– The controller’s DEBUG port is connected to your PC using a USB-to-micro USB cable.
– Power is currently applied to the controller.
44 August 14, 2023