Chapter 3 Platform services and administration EC-BOS-9 Install and Startup Guide
Step 1 In the Nav tree, expand the station’s Services→PlatformServices, and double-click
DataRecoveryService.
The Data Recovery Service Editor window opens.
By default, the Service Enabled property is true. This is appropriate since the controller has no
backup battery installed.
Step 2 If a battery-less controller is powered from a battery-backed UPS, you could also choose to set Serv-
ice Enabled to false.
If you set Service Enable to false, the DataRecoveryService no longer records runtime data-
base changes to SRAM but depends entirely on its backup battery to preserve station data upon a
power loss!
Step 3 To write the configuration to the host platform, click Save.
You are prompted to reboot now to apply the changes.
Step 4 To reboot with the change in the DataRecoveryService (disabled or enabled) made effective, click
Yes.
Performing platform administration
The Commissioning Wizard performs most platform configuration tasks. After running the wizard, you may re-
view and change configuration options using the Platform Administration view.
Prerequisites:
The EC-BOS controller is already commissioned using the Commissioning Wizard. You have admin rights to
configure the platform.
You have admin rights to configure the platform.
Step 1 Using EC-Net 4 Pro, open a platform connection to the EC-BOS controller. Use the platform creden-
tials you specified when creating a platform user while commissioning the controller.
Step 2 Right-click Platform, double-click Platform Administration and enter your platform credentials.
The Platform Administration view opens.
34 August 14, 2023