Digital Monitoring Products, Inc. | Troubleshooting Guide 27
ZONE STATE
This Diagnostics function allows you to enter any zone number and check the zone’s current state (Normal, Open, or
Shorted)�
1
At the [ZONE STATE] display, press any Select key
2
The display changes to [ZONE NUMBER:-]
3
Enter in the zone number you want to check and press CMD� The panel displays the zone name (first ten
characters only) and the current state of the zone as NORML (normal), OPEN, or SHORT
Example: [FRONT DOORNORML] - When the state of the zone changes, the display also changes to
reflect the change
The ZONE STATE feature is a much better way to troubleshoot zone problems than the Zone Status function in the User
Menu because the ZONE STATE display remains until you exit back into the Diagnostics menu and updates in real time�
ZONE PARAMETERS PANEL ZONES 1-8 & MODEL 711, 712 & 714 EXPANDER ZONES
ZONE CONDITION RESISTANCE ON ZONE VOLTAGE ON + TERMINAL
OPEN More than 1300 Ohms Over 2�0 VDC
NORMAL 600 – 1300 Ohms 1�2 – 2�0 VDC
SHORT Less than 600 Ohms Under 1�2 VDC
LX-BUS STATUS
The fourth Diagnostic function is the LX-BUS STATUS� This function allows the panel to poll all devices connected to the
LX-Bus of an interface card and check for any OVERLAP, MISSING, or EXTRA addresses�
1
At the [LX-BUS STATUS] display, press any Select key
2
The display changes to [OVLP MIS EXT]� Press the Select key below the status you wish to check� See the
illustration below for more detail�