DOD Technologies, INC • 675 Industrial Dr. Bldg. A • Cary, IL 60013 • Phone (815) 788-5200 • Fax (815) 788-5300
Innovative Life Safety Systems & Services
Low Flow - Verify Tray Insertion
The flow is low for multiple points on an
analyzer.
1. Verify analyzer is
fully inserted.
2. Make sure all
points are flow
balanced. 3.
Refer to Flow Path
verification procedure
Interruption during Modbus
communication process.
1. Power cycle unit
2. Contact DOD
Technologies, Inc.
Optic Block Comm. Failure
Communication interruption between
optic block and PC.
1. Refer to Optic
Troubleshooting
Procedure.
Communication interruption between
Flow board and PC.
1. Refer to Flow
Comm. Fault
Procedure.
Micro switch failed to open during a
tape advance.
1. Refer to Gate Fault
Procedure.
Micro switch failed to close during a
tape advance.
1. Refer to Gate Fault
Procedure.
Setting DAC to preset values
CL96 was unable to set DAC values back
to previously retained values.
Block Below Minimum Voltage
Optic block voltage dropped below the
required voltage of 5.1 V
1. Verify 5V supply is
turned up to 6.1 VDC
2. Verify all optic
blocks have at least
5.4 VDC
3. See Optic
Troubleshooting
Procedure
Output Module Failure or Not
Installed
Expected I/O module cannot be located
by the PC.
1. Refer to I/O
Verification
Procedure.
Retentive Memory Error, History
and/or Tape counters may be
corrupt.
Unable to load previous historical
events after power cycle.
CL96 was left out of analysis for a time
frame that overlapped the time out
setting.
1. Check to see if a
fault caused the CL96
to leave analysis
2. If not put the CL96
back into analysis