2358-065 Issued 7-19
Version E
A second communication
line can be added with same
wiring limitations shown in
examples if desired.
tracker
expansion
board
address 3
tracker
expansion
board
address 6
tracker
expansion
board
address 7
tracker
expansion
board
address 8
tracker
expansion
board
address 9
tracker
expansion
board
address 11
All boards are 2000 ft or less away from access control system.
250 ft 250 ft 1500 ft
Zone Addresses
50 ft
55 ft
55 ft
400 ft
50 ft 130 ft
access control system
tracker
expansion
board
address 3
relay 2/wiegand 2
relay 1/wiegand 1
Example 7: 4000 ft total,
ONLY one HARDwired communication line shown. 24 boards with “Zones” are connected to relay 2/wiegand 2.
Communication line to boards are connected
in parallel. Allows “teeing” of communication
cable for optimal cable routing.
Relay/Wiegand Note:
Relay 2/wiegand 2 MUST be connected to tracker
expansion board addresses 3 thru 10.
Relay 1/wiegand 1 connects to tracker expansion board
addresses 11 thru 18 if that many boards are desired.
Wiring More Than 8 Boards Note:
Use 6 conductor stranded with overall shield - 18 gauge. ONLY use 18
gauge when wiring more than 8 boards.
DO NOT connect shield to 2358-010 board common.
DO NOT use twisted pair.
tracker
expansion
board
address 4
tracker
expansion
board
address 4
tracker
expansion
board
address 4
tracker
expansion
board
address 4
Quad Box
farthest
board
2000 ft
away
100 ft 1000 ft
Zone Addresses
tracker
expansion
board
address 9
Zone Addresses
Zone Addresses
tracker
expansion
board
address 10
tracker
expansion
board
address 10
tracker
expansion
board
address 10
tracker
expansion
board
address 10
Quad Box
farthest
board
1500 ft
away
Zone Addresses
tracker
expansion
board
address 12
tracker
expansion
board
address 12
tracker
expansion
board
address 12
tracker
expansion
board
address 12
Quad Box
farthest
board
180 ft
away
tracker
expansion
board
address 5
tracker
expansion
board
address 5
100 ft 20 ft 20 ft 20 ft
tracker
expansion
board
address 5
tracker
expansion
board
address 5
Zone Addresses
farthest
board
160 ft
away
relay 2/wiegand 2
relay 1/wiegand 1
Individual addresses can be used if desired.
Individual addresses can be used if desired.
tracker
expansion
board
address 3
tracker
expansion
board
address 3
500 ft 600 ft 400 ft 500 ft
tracker
expansion
board
address 3
tracker
expansion
board
address 3
tracker
expansion
board
address 4
tracker
expansion
board
address 4
500 ft 600 ft 400 ft 500 ft
tracker
expansion
board
address 4
tracker
expansion
board
address 4
Zone Addresses
Zone Addresses
A second communication
line can be wired with the
same wiring limitations shown
in examples if desired.
access control system
NO more boards can be connected to reley 2/wiegand 2 communication line.
Example 6: 4000 ft total, ONLY one HARDwired communication line shown. 8 boards
with “Zones”
are connected to relay 2/wiegand 2.
Communication line to boards are connected in
parallel. Allows “teeing” of communication cable
for optimal cable routing.
farthest
board
2000 ft
away
farthest
board
2000 ft
away
IMPORTANT Wireless communication maximum distances between the access control system and tracker expansion
boards will vary from the HARDwire run distances illustrated above. See the instruction sheets in the wireless kits and the
Layout and Start-Up Procedure for the correct distances between the hardware when using wireless communication.