UIC-DX270 Series User’s Manual Rev 1.0
- 26 -
4) RUN INFORMATION
Item Description Units Step Min Max Default View Access
000 Inlet Temp. ℃ 0.1 -40.0 70.0 View only USER 1 -
001 Outlet Temp. ℃ 0.1 -40.0 70.0 View only USER 1 -
002 Discharge Gas Temp. ℃ 1 0 180 View only USER 1 -
003 Run hour h 1 0 99999 0 USER 1 SVC 2
004 Comps run hour h 1 0 99999 0 USER 1 SVC 2
005 Comps on/off number 1 0 99999 0 USER 1 SVC 2
1) Over 99999 Operation Time or Number, it is initialized ‘0’ automatically.
2) Operation Time or Number could be changed over Service Level 2.
5) OPERATION
Item Description Units Step Min Max Default View Access
100
Set value
℃
0.1 -99.9 99.9
7.0
USER2 USER2Bar 2.0
% 20.0
101
Run differential
℃
0.1 +0.1 +50.0
+5.0
USER2 USER2Bar +2.0
% +30.0
102
Stopping differential
℃
0.1 -50.0 0.0
0.0
USER2 USER2Bar 0.0
% 0.0
103
50% cap.differential
℃
0.1 0.0 +50.0
+1.0
SVC1 SVC1 Bar +0.5
% +10.0
104
75% cap.differential
℃
0.1 0.0 +50.0
+2.0
SVC1 SVC1 Bar +1.5
% +20.0
105
○
+
D.Band differential
℃
0.1 0.0 +20.0
+0.2
SVC1 SVC1
Bar +0.1
% +2.0
106
○
-
D.Band differential
℃
0.1 -20.0 0.0
-0.2
SVC1 SVC1
Bar -0.1
% -2.0
107
Injection set value. ℃ 1 0 180 100 SVC1 SVC1