5.3.3 Variable Speed Control Wiring for Red
Jacket
Figure 5-5 Red Jacket Wiring for Variable Speed Control
5.3.4 Typical Red Jacket Wiring Connections
Figure 5-6 Red Jacket Wiring Connections
5.3.5 LIM Addressing
LIM modules must be assigned a unique identification number.
Module numbers must be unique within the Module Group; that is, it
is possible assign the same number to both a LIM Module and to an
OM4 Module, but it is not possible to assign the same number to more
than one LIM Module or to more than one OM4 Module. The module
numbers are used when the system is configured. Refer to the
“M1801 SiteSentinel
®
Integra™ Configuration Manual” for details
about system setup
A small, white rotary switch is located at the top of the
PC board inside each module. The switch has 10
positions, marked “0” to “9.” A small arrow on the switch
points to the current position. Default switch setting is
“1.”
NOTE: Although the switch has 10 settings, only settings 1-8 are
valid. DO NOT set the switch to either “0” or “9” – the module will
NOT be recognized by the system.
Follow these steps to set the Petro-Net™ address:
1. Turn the module power OFF.
2. Use a ¼-inch (6 mm) blade screwdriver to gently
rotate the rotary switch to the desired location.
3. Turn the module power to ON.
CAUTION: Do not change the module number while the LIM module
power is ON.