*NOTE: Maximum Wiring Length is the maximum length of cable to 
be used to connect all sensors on an individual channel. This length 
includes run of cable from I.S. Barrier to each sensor board in the 
string. 
 
Hydrocarbon Vapor Sensor 
OPW P/N: 30-3222 
 
Hydrocarbon Vapor Sensor 
The Hydrocarbon Vapor Sensor is designed to detect hydrocarbon 
vapors in dry monitoring wells. The presence of these vapors could 
indicate a potentially dangerous leak that could lead to safety and 
environmental problems. 
The sensor is made from a long-life resistive element that increases 
dramatically  in  resistance  in  the  presence  of  hydrocarbon  vapors. 
After the vapors have dissipated, the sensor returns to normal and is 
ready to detect hydrocarbon vapors again. This process could take 
up to 30 minutes depending on the saturation factor. In the event of a 
break in the cable or any sensor malfunctions, the system will activate 
the alarm. 
Hydrocarbon Vapor Sensor Installation  
1.  Check Dry Monitoring Wells for vapors before installing. 
2.  Mount Sensor close to the top, above the water level, if 
applicable. 
3.  If sensor is submerged in water it will not function.