Doc. #: M1800, Rev. 06
Page 66 of 101
Dual-Float Dispenser Sump Sensor
OPW P/N: 30-0232-D-10
Dual-Float Sump Sensor
This Dual-Float Sensor is the same as a Discriminating Dispenser
Pan Sensor, Part No. 30-0232-DH-10, but without Belcor
®
inside the
sensor. This makes it non-discriminating.
*NOTE: Maximum Wiring Length is the
maximum length of cable to be used to connect all sensors on an
individual channel. This length includes run of cable from I.S. Barrier
to each sensor board in the string.
Dual-Float Dispenser Sump Sensor Specifications
Low Liquid, High Liquid, Fuel
-40°F to 158°F (-40°C to +70°C)
Length: 11.1” (28.2 cm), Diameter: 2.3” (5.8 cm)
Low: 1.5” (3.8 cm), High: 8” (20.3 cm)
Belden #88760 or Alpha #55371
1,000’ (305 m) field wiring
16 per I.S. barrier channel (64 per barrier)
Red = Power, Black = Signal, Shield = Ground
Without Belcor
®
Inside Sensor