EasyManua.ls Logo

Dover OPW SiteSentinel Integra 100 - Interstitial Hydrocarbon Liquid Sensor with Water Indicator

Dover OPW SiteSentinel Integra 100
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Doc. #: M1800, Rev. 06
Page 64 of 101
www.opwglobal.com
Interstitial Hydrocarbon Liquid Sensor with
Water Indicator
OPW P/N: 30-0234-HW-01
Interstitial Hydrocarbon Liquid Sensor Installation
The Interstitial Hydrocarbon Liquid/Water Sensor is designed for use
in the interstitial area of a fiberglass double-walled tank. The
hydrocarbon liquid/water sensor contains a carbon/polymer material
that changes its resistance when exposed to liquid hydrocarbons.
Additionally, it contains a conductive strip to detect the presence of
water, providing the ability to discriminate between hydrocarbon liquid
and water. In the event of a break in the cable, the system will activate
the alarm.
Interstitial Hydrocarbon Liquid/Water Sensor Specifications
Detects:
Liquid hydrocarbons/water
Operating Temperature:
-40°F to 158°F (-40°C to +70°C)
Dimensions:
Length: 13.8” (35 cm), Width: 1.0” (2.5 cm)
Nominal Resistance:
Uncontaminated: 1000-3000 ohms
Contaminated: 10,000-200,000 ohms
Cable Requirements:
Belden #88760 or Alpha #55371
Maximum Wiring Length*:
1,000’ (305 m) field wiring
Multi-Drop Restriction:
16 per I.S. barrier channel 64 per barrier)
Connections
Red = Power, Black = Signal, Shield: = Ground
*NOTE: Maximum Wiring Length is the maximum length of cable to
be used to connect all sensors on an individual channel. This length
includes run of cable from I.S. Barrier to each sensor board in the
string.

Table of Contents