OM4 Output Module Wiring
As shown below, connect the red and black wires from the 20-1582 cable to the first OM4 Output Module’s
POWER terminals (order not important). Connect the green (or brown) wire to the SIGNAL terminal.
NOTE: When installing two (2) OM4 Output Module boxes, cut off the round DIN end of the remaining 20-
1582 cable and use it to daisy-chain the POWER and SIGNAL terminals together. Route this cable through
the conduit connecting the boxes installed earlier.
1. Connect all relay field wiring to the correct
terminal block(s).
2. When installing two OM4 Output Module
boxes, place the address jumper on the
second OM4 on the second row of pins as
shown at right. To do this, take off the four
nuts securing the aluminum cover and
remove it, exposing the circuit board. Set
the jumper and replace the cover.
3. Reinstall each cover/module assembly to
their boxes.