6● DYNALOGIX II (DY 4000) DYNACO USA
40 THE SAFEST CHOICE Slimline Series RevB.doc1
6.3.3 Set Automatic Timers
The Open Run Timer and Close Run Timer act as a failsafe to prevent the door from running
continuously when the open or close limit switch fails to stop the door. These timers should be set
for a period that exceeds the duration of a full open or close cycle.
• Press and release the OPEN run timer button. Opening_Time=## displays in the LCD. See
Figure 6-17.
Open/Close
Run Timers
M-00095
06/13/05
JOG
UP/RESET
JOG
DOWN
CLOSE
OPEN
MC/PB
MENU
ENTER
CLOSE
TIMERS
AC/LOOP
PROGRAM
RUN
TIMERS
MESSAGE DISPLAY COUNTER
MESSAGE DISPLAY COUNTER
Opening
Time=##
Figure 6-17: RUN TIMERS buttons
• Press and release the PROGRAM buttons to change the countdown time to the desired
duration. See Figure 6-18.
Increase
Setting
M-00096
06/09/05
JOG
UP/RESET
JOG
DOWN
CLOSE
OPEN
MC/PB
MENU
ENTER
CLOSE
TIMERS
AC/LOOP
PROGRAM
RUN
TIMERS
Decrease
Setting
Figure 6-18: Adjust Countdown Time
• The DYNALOGIX II automatically saves the changes.
• Press and release the CLOSE run timer button. Closing_Time=## displays in the LCD.
• Press and release the PROGRAM buttons to change the countdown time to the desired
duration. The DYNALOGIX II automatically saves the changes.