DH200F User Manual
©Dyness reserves the copyright of this document
2727
capacity and without any vegetation cover. The storage ground should be flat, no water
accumulation, no bumps or unevenness, and the flatness should be no more than 5mm.
Storage environment temperature: 0
o
C~+35
o
C, storage environment relative humidity:
0~95%, no condensation.
Pay attention to cope with the harsh environment around, such as sudden cold, sudden
heat, collision, etc., so as not to cause damage to the Pack.
The air inlet and outlet of the product should be effectively protected, while effective
measures should be taken to prevent rain, sand and dust from intruding into the
interior of the cabinet.
Storage Operating Requirements
Packing boxes should not be tilted or inverted.
Make sure that the cabinet doors and internal equipment cabinet doors are securely
locked before storage.
Must raise the base of the cabinet, the specific height of elevation should be
determined reasonably according to the site geology, weather and other conditions.
Additionally, heating should be provided for internal equipment in low-temperature
environments.
For products stored for a long period (more than six months), perform a visual
inspection by opening the cabinet doors. Check for any condensation on the exterior of
the cabinet and ensure the cabinet and internal equipment are intact. Additionally,
perform checks after powering on and starting up. If necessary, professional testing
should be conducted before installation.
Perform regular inspections at least every two weeks to check the cabinet and internal
equipment for any damage. Prevent insect or rodent infestation. If any damage is found,
replace the packaging immediately.
NOTE
Starting from the date of delivery, if the storage period for the PACK exceeds six
months under the above conditions, perform one charge and discharge cycle to achieve
a system SOC of 30% to 40%. After recharging, maintain consistent SOC levels.