Eaton 9155 UPS (8–15 kVA) User’s Guide 164201553—Rev H0 13
Table 2. UPS Cabinet Weights
Standard Model Floor Loadings (2-High/3-High Cabinets)
Eaton 9155
Maximum
Weight (lb)
Point Loading
(lb/in
2
)
Distributed Loading
(lb/ft
2
)
2-High UPS
352 88 166
3-High UPS
590 148 278
2-High UPS with Maintenance Bypass Module
(MBM) or Power Distribution Module (PDM)
3-High UPS with MBM/PDM
3-High UPS with Isolation Transformer
558 140 263
2-High EBM
480 120 226
3-High EBM
710 178 335
The UPS cabinet uses forced air cooling to regulate internal component temperature. Allow clearance in front
of and in back of the cabinet for proper air circulation. The clearances required around the UPS cabinet are
shown in the following table.
Table 3. UPS Cabinet Clearances
From Front of Cabinet 36” (91.4 cm) working space
From Back of Cabinet
6” (15.2 cm) without an MBM/PDM installed; with an MBM/
PDM installed, clearance is determined by the customer-
supplied mating
UPS Installation Plan and Unpacking