EasyManua.ls Logo

Eaton 9155 UPS - Table 10. User Settings

Eaton 9155 UPS
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton 9155 UPS (8–15 kVA) User’s Guide 164201553—Rev H0 69
Table 10. User Settings
Description
Available Settings Default Setting
Set Date and Time Set Month
Date: mm/dd/yyyy
Time: 24:00
01/01/2003
00:00
Display Contrast Adjust contrast with up/down arrow
buttons
Moderate
Change Language Select Language: <English>
Elegir idioma <Español>
English
Relay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-
Slot 2-1/2/3/4]
Setup: [Battery Low] [On Battery] [On
Bypass] [UPS ok] [custom] [empty]
Alarm 1: empty
X-Slots (1 or 2)
#1: UPS ok
#2: On Bypass
#3: Summary Alarm
#4: On Battery
Signal Inputs [empty] [Logic]
(see paragraph
6.3.3 Programmable Signal Inputs for more
information. )
<empty>
Serial Port Config Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
19200
Modem Config Modem Installation <Not Installed>
Set Modem Call Events Event #0
Call modem: no
Set Modem Init String ATZ0
Set Modem Call Command
None
Set Modem Communication Password
None
Start Screen Eaton logo
Mimic screen
Eaton logo
User Password Enabled/Disabled
If Enabled is selected, the password is
USER.
Disabled
Audible Alarms Normal Sound/Disabled Normal Sound
Battery Charging ABM cycling/constant ABM cycling
Automatic Battery Tests Enabled/Disabled
Enabled automatically runs the battery test
once a month.
Enabled
Full Power Battery Test Enabled/Disabled Enabled
Number of Battery Strings 0 through 22
(see paragraph
7.5 Configuring the UPS for EBMs for more
information. )
2 strings for UPS-32 models
4 strings for UPS-64 models
UPS Operating Instructions

Table of Contents

Related product manuals