Table 2. UPS Cabinet Weights (Continued)
Standard Model Floor Loadings (2-High/3-High Cabinets)
Eaton 9355 UPS
Maximum Weight
Point Loading
lb/in
2
(kg/cm
2
)
3-High UPS-64 619 lb (281 kg) 155 (10.9)
2-High EBM
480 lb (218 kg) 120 (8.4)
3-High EBM
710 lb (322 kg) 178 (12.5)
The UPS cabinet uses forced air cooling to regulate internal component temperature. Allow clearance in front
of and in back of the cabinet for proper air circulation. The clearances required around the UPS cabinet are
shown in the following table.
Table 3. UPS Cabinet Clearances
From Front of Cabinet
36" (91.4 cm) working space
From Back of Cabinet
6" (15.2 cm) without PDM installed; with PDM installed, clearance determined by
customer-supplied mating plug
From Right of Cabinet Refer to local codes for right side service access [minimum 36" (91.4 cm)]