Eaton 9355 UPS (10/15 kVA) User’s Guide 164201594—Rev H0 25
Table 4. Eaton 9355 10–15 kVA UPS: Recommended Terminal Block Wiring
Model
Voltage
Wire
Function
Feeder
Circuit
Breaker
Rating
L1, L2, L3,
N Wire
Size
1
Ground
Wire
Size
1
Tighten-
ing
Torque
Conduit Size
2, 3
(Number of
Conduits)
Eaton 9355 10
kVA
UPS System
208 Input
UPS
Module,
TB1
WYE / 4-
Wire
45A 6 AWG 10 AWG
120 lb in
(13.5 Nm)
1.00" conduit
(1)
220
480 Input
XFMR
Module
Delta / 3-
Wire
20A 12 AWG
12 AWG
120 lb in
(13.5 Nm)
1.00" conduit
(1)
600 14 AWG
208
Output
UPS
Module,
TB1
WYE / 4-
Wire
6 AWG 10 AWG
120 lb in
(13.5 Nm)
1.00" conduit
(1)
220
480 (with
transformer)
8 AWG 10 AWG
120 lb in
(13.5 Nm)
1.00" conduit
(1)
600 (with
transformer)
UPS Installation Plan and Unpacking