Eaton 9355 UPS (10/15 kVA) User’s Guide 164201594—Rev H0 27
Table 5. Eaton 9355 10–15 kVA UPS with Version 1 Wall-Mounted Bypass Switch: Recommended Terminal Block Wiring
Model
Voltage
Wire
Func-
tion
Feeder
Circuit
Breaker
Rating
L1, L2,
L3,
N Wire
Size
1
Ground
Wire
Size
1
Tighten-
ing
Torque
Conduit Size
2, 3
(Number of
Conduits)
Eaton 9355 10
kVA
UPS System
208
Input
45A
6 AWG
10 AWG
120 lb in
(13.5 Nm)
1.00" conduit (1)
220
8 AWG
208
Output
8 AWG 10 AWG
120 lb in
(13.5 Nm)
1.00" conduit (1)
220
Eaton 9355 15
kVA
UPS System
208
Input
60A 4 AWG 10 AWG
120 lb in
(13.5 Nm)
1.25" conduit (1)
220
208
Output
6 AWG 10 AWG
120 lb in
(13.5 Nm)
1.00" conduit (1)
220
1
Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-104(A).
Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long
service runs. Follow local requirements.
2
Per NEC article 300 20(a) for Ferrous Metal Raceways, all three-phase conductors must be run in the same conduit. Neutral and
ground must be run in the same conduit as the phase conductors.
3
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG ground conductor.
If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the conduit needed to
accommodate the extra wire or size and use that conduit size in place of the conduit size listed. Conduit sizes were chosen from
NEC Table C1, type letters RHH, RHW, RHW 2, TW, THW, THHW, THW 2.
UPS Installation Plan and Unpacking