9A UPS 1-3K
The following table displays the options that can be changed by the user:
Submenu Available seng Default seng
OPV
[230] [240] [220] [230]
OPF
[ASF] [50] [60] [ASF]
bYPA
[000] [001]
[000]
MOdE
[UPS] [ECO] [CVF] [UPS]
EbPN
[000] [001] [002] [003][004] [005] [006] [007] [008] [009] [000]
bATT
[000] [001]
[000]
Note
Here [000] means Bypass Disable,[001] means Bypass Enable.
Here [000] means baery remaining me funcon is disabled. [001] means baery
remaining me funcon is enabled, then in baery mode or baery test mode the baery
remaining me (in unit Min) and string “bATT” would display on LCD in turn every 2s.
In bypass or standby mode, pressing the “Enter” buon on the LCD panel for more than
one second to enter seng mode. The LCD display is shown in the following diagram. The
string “OPVindicates that the current seng is output voltage. “230Vac” indicates the cur-
rent default output voltage is 230Vac. if you want to set output voltage, press the “Enter”
buon for more than one second, a ickering string “230” would be shown, if the “Enter
buon is pressed again, the string “230” turn to ickerless, the output volt is changed to
230V; if the “Selectbuon is pressed for more than one second, the next ickering string
“240” appear, the order of ickering string is 230-240-220, Press “Enter” buon to conrm
the output volt what you want.
Exit the setting mode to short touch the “Enter” button; continue setting to press “Select”
button. if no any pressing on the “Select” or “Enter” button lasting for more than 10
seconds, the setting mode exit automatically.
Hz
Vac
+
OUTPUT LOAD
INPUT BATTERY