9A UPS 1-3K
!
Warning: take care not to reverse the polarity + (red) and - (black) when connecting
the batteries as this will destroy the device.
Testing new batteries
To test new baeries:
1. Charge the baeries for 48 hours.
2. Press “ON” buon f
or more than 1 second, the UPS would detect whether the
baery is connected or the baery is low immediately.
3. The UPS starts a baery test if the baeries are fully charged, the UPS is in Normal mode
with no acve alarms, and the bypass voltage is acceptable. the UPS transfers to Baery
mode and discharges the baeries for 10 seconds, the front panel displays "TEST".