36
9A UPS 1-3K
8.2 Electrical output
All models Normal mode High Eciency mode Baery mode
Voltage regulaon ±1% ±1%
Eciency (1K/2K/3K) 90%/90%/91% Up to 97% Up to 85%
Nominal output 220/230/240V
Nominal Frequency 50Hz or 60Hz, autosensing or congurable as a frequency converter
Output overload
(Tower)
[100-105%] overload warning
[105-130%]*, 60 sec
[130-150%]*, 10 sec
>150% Shutdown immediately
[100-105%] overload warning
[105-130%], 60 sec
[130-150%], 1 sec
>150% Shutdown immediately
Output overload
(Rack)
[100-102%] overload warning
[102-130%]*, 12 sec
[130-150%]*, 1.5 sec
>150% Shutdown immediately
[100-102%] overload warning
[102-130%], 12 sec
[130-150%], 1.5 sec
>150% Shutdown immediately
Short circuit current
limitaon
Depend on the external fuse or breaker in
the upstream of UPS
1K: 12A < 7cycles
2K: 26A < 7cycles
3K: 40A < 7cycles
Voltage waveform Sin wave
Harmonic distoron
< 2% THDV on linear load
< 6% THDV on non-linear load
Power Factor 0.9
* Transfer to bypass if bypass is OK, else cut o the output.
8.3 Baery
Internal baeries EBM
Specicaons
9A1000I & 9A1000IR: 24Vdc - 2 x 12V, 9Ah
9A2000I & 9A2000IR: 48Vdc - 4 x 12V, 9Ah
9A3000I & 9A3000IR: 72Vdc - 6 x 12V, 9Ah
9AEBM24: 24Vdc - 3 x 2 x 12V, 3 x 9Ah
9AEBM48: 48Vdc - 3 x 4 x 12V, 3 x 9Ah
9AEBM72: 72Vdc - 2 x 6 x 12V, 2 x 9Ah
9AEBM24R: 24Vdc - 3 x 2 x 12V, 3 x 9Ah
9AEBM48R: 48Vdc - 2 x 4 x 12V, 2 x 9Ah
9AEBM72R: 72Vdc - 2 x 6 x 12V, 2 x 9Ah
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3 - 5 years oat
service life at 25°C (77°F)