9A UPS 1-3K
6 UPS maintenance
6.1 Equipment care
• For the best prevenve maintenance, keep the area around the equipment clean and
dust free. If the atmosphere is very dusty, clean the outside of the system with a vacuum
cleaner.
• For full baery life, keep the equipment at an ambient temperature of 25°C (77°F).
If the UPS requires any type of transportaon, verify that the UPS is disconnected
and turned o.
The baeries are rated for 3-5 years service life. The length of service life varies, depend-
ing on the frequency of usage and ambient temperature (life divided- by 2 each 10°C
above25°C).
Baeries used beyond expected service life will oen have severely reduced runmes. Re-
place baeries at least every 4 years to keep units running at peak performance.
Baeries runme will be reduced at low temperature (below 10°C).
6.2 Storing the equipment
If you store the equipment for a long period, recharge the baery every 6 months by con-
necng the UPS to ulity power. The internal baeries charge to 90% capacity in less than 3
hours. However, Eaton recommends that the baeries charge for 48 hours aer long-term
storage.
Check the baery recharge date on the shipping carton label.
If the date has passed and the baeries were never
recharged, do not use them. Con-
tact your service representave.
6.3 When to replace baeries
Eaton UPS baeries have an expected life span of 3-5 years. Aer 4 years operaon, you
should take proacve steps to ensure baeries replacement for opmal operaon and reli-
ability,contact your service representave to order new baeries.
6.4 Replacing baeries
For baery replacement, follow Eaton instrucons provided on www.eaton.eu/Baery-
Services.
!
DO NOT DISCONNECT the baeries while the UPS is in Baery mode.
UPS needs to be turned o and fully disconnected before replacing baeries.