37
9A UPS 1-3K
8.4 Environmental and safety
Standards
IEC62040-1:2008+A1:2013, EN IEC 62040-1: 2019+A11:2021
EN/IEC 62040-2 Electromagnec Compability EMC (UPS EMC), category C2
IEC/EN 62040-3 Performance
EMC (Emissions)
CISPR32 Class A
IEC/EN 61000-3-2 Flickers
IEC/EN 61000-3-3 Harmonics
EMC (Immunity)
IEC 61000-4-2, (ESD): 4kV Contact Discharge / 8kV Air Discharge
IEC 61000-4-3, (Radiated eld): 10V/m
IEC 61000-4-4, (EFT): 2kV
IEC 61000-4-5, (Surges): 1kV Dierenal Mode/2kV Common Mode
IEC 61000-4-6, (Electromagnec eld): 10V
IEC 61000-4-8, (Conducted magnec eld): 30A/m
UPS enclosure IP rang IP20
Earthing system
This UPS can be connected to TN, TT, IT electrical supply system, same system is
supplied to the load
Operang temperature
0 to 40 °C (32 to 104 °F) in Online mode, with linear derang for altude
Note: thermal protecon switches load to Bypass in case of overheang
Storage temperature
0 to 40 °C (32 to 104 °F) with baeries
-15 to 55 °C (5 to 130 °F) without baeries
Relave humidity 0 to 95 % (without condensaon)
Operang altude
Up to 3,000 meters (9,843 ) above sea level, no derang for 40°c (104°F) room
temperature
Audible noise < 50 dBA at 1 meter typical
* For output cable < 10m.
*The load derang 1 % every up 100m @1000~3000m.