33
9A UPS 1-3K
Condions Possible cause Acon
Emergency supply period shorter
than norminal value.
Baeries not fully
charged / baeries
defect.
Charge the baeries for at least 5 - 8 hours and
then check capacity. If the problem sll persists,
consult your dealer.
Fan fail. Fan abnormal. Check if the fan is running.
Baery over voltage. Baery is over charged.
Stop charging to baery automacally, and aer
the baery voltage is normal and the mains is
normal, charge automacally again.
Baery low. Baery voltage is low.
When audible alarm sounding every second,
baery is almost empty.
Charge fail. The charge is broken. Nofy dealer.
Inverter temperature high.
Inside temperature of
the UPS is too high.
Check the venlaon of the UPS, check the
ambient temperature.
Ambient temperature high.
The ambient
temperature is too high.
Check the environment venlaon.
Baery open.
Baery pack is not
connected correctly
Check the baery bank is connected to the UPS.
Check the baery breaker is turn on.
Baery fault.
Baery may need to be
replaced.
Nofy dealer.
Overload. Overload.
Check the loads and remove some non-crical
loads.
Check whether some loads are failed.
Site fail.
Phase and neutral
conductor at input of
UPS system are reversed.
Rotate mains power socket by 180° or connect
UPS system.
EPO acve. EPO funcon is enabled. Turn o the EPO switch.
Bus fault
(Low/high/ Unbalance/so
start).
UPS internal fault. Nofy dealer.
Inverter fault
(Low/high/so start).
UPS internal fault. Nofy dealer.
Over temperature fault. Over temperature.
Check the venlaon of the UPS, check the
ambient temperature and venlaon.
NTC open. UPS internal fault. Nofy dealer.
Inverter short. Output short circuit.
Remove all the loads. Turn o the UPS. Check
whether the output of UPS and loads is short
circuit. Make sure the short circuit is removed,
and the UPS has no internal faults before turning
on again.
Bus short. UPS internal fault. Nofy dealer.