PROFIBUS I/O Parameters
34 C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Input 2 Scaled Three-Phase Currents in
deciamps—Line
L3 RMS current in 0.1 Amps
Input 4 Average RMS AC Current—Pole Average RMS Pole Current (Float)
Input 4 Three-Phase RMS Current on the Pole
itself
L1 RMS Pole Current (Float)
Input 4 Three-Phase RMS Current on the Pole
itself
L2 RMS Pole Current (Float)
Input 4 Three-Phase RMS Current on the Pole
itself
L3 RMS Pole Current (Float)
Input 2 Scaled Average Three-Phase Currents in
amps—Pole
Scaled Average pole current in Amps
Input 2 Scaled Three-Phase Currents in amps—
Pole
L1 RMS pole current in Amps
Input 2 Scaled Three-Phase Currents in amps—
Pole
L2 RMS pole current in Amps
Input 2 Scaled Three-Phase Currents in amps—
Pole
L3 RMS pole current in Amps
Input 2 Scaled Average Three-Phase Currents in
deciamps—Pole
Scaled Average pole current in 0.1 Amps
Input 2 Scaled Three-Phase Currents in
deciamps—Pole
L1 RMS pole current in 0.1 Amps
Input 2 Scaled Three-Phase Currents in
deciamps—Pole
L2 RMS pole current in 0.1 Amps
Input 2 Scaled Three-Phase Currents in
deciamps—Pole
L3 RMS pole current in 0.1 Amps
Input 2 Power Factor 0 to 1.0000 (in 0.0001)
Input 2 Integer Average Three-Phase Real
Power kW
Average Real Power (kW)
Input 6 Power Device Pole Temperature L1 pole temp in 0.1 °C
L2 pole temp in 0.1 °C
L3 pole temp in 0.1 °C
Input 2 DC Control Voltage DC voltage reported in 0.001 V
Input 2 Device Temperature in Degrees C Device temp in 0.1 °C
Input 2 Auto Reset Count # of times S811+ has been auto reset
Input 2 Line Frequency Line Frequency (in 0.01 Hz)
Input 1 Line Phase Sequence 0x01 = ABC Phase sequence
0x02 = ACB Phase sequence
Input 20 Fault List Last 10 Fault/Warning Codes
Input 2 Application Status Applications status (present fault)
Input 1 Motor Inputs Level Sense Enabled 0x00 = edge sense
0x01 = level sense
Input 4 Firmware Version List
Input 2 Hardware Version List
Table 25. S811+ Available IO Data for Cyclic Polling, continued