Page 4-17
IL17569
Effective June, 2001
Logging
Current Demand
Power Demand
Event Log Enable
Data Logger
Waveform Capture
“Logging” Display:
Datalogger
Mode: Cont.
Trigger: Auto
Interval (s): 900
Value 1: IA
Value 2: IB
Value 3: IC
Value 4: IX
Value 5: VA
Value 6: VB
Value 7: VC
Value 8: VX
“Datalogger” Display:
Power Demand
Window: Fixed
Interval (m): 15
“Power Demand” Display:
Current Demand
Interval (m): 15
“Current Demand” Display:
Event Log Enable
I Pickup: Yes
V Pickup: No
Freq Pickup: No
PF Pickup: No
Unbal Pickup: No
SYSALM Pickup: No
Cin1: No
Cin2: No
Cin3: No
Cin4: No
Cin5: No
Cin6: No
Cin7: No
Cin8: No
Comm.: No
“Event Log Enable” Display:
Waveform Capture
Records: 16 X 16
PreTrigger: 2
OSC Trigger
“Waveform Capture” Display:
Logging
Contact Input CFG
Contact Input CFG
Cin1: 52a
Cin2: 52b
Cin3: BFI
Cin4: Bkr Trouble
Cin5: Remote Open
Cin6: Remote Close
Cin7: Remote Reset
Cin8: user defined
“Contact Input CFG” Display:
BFI- “Breaker Fail Initiate”
OSC Trig Enable
TRIP 2: Overwrite
DV/VI: Disable
Logic LG6: Overwrite
OSC Trig Enable
Cntrl PB: Overwrite
Comm: Overwrite