Page 5-15
IL17569
Effective June, 2001
Table 5.4 Logging Settings Phase time overcurrent (51P) and instantaneous (50P-1 & 50P-2) device settings
Display Setting Description Setpoint Range/ Default Selected Refer to
Value Selection Setting Value Sec. #
Current Demand Current Demand Logging Setting 5.5.4
Interval (m): Select interval for taking current 1 to 60 minutes 15 5.5.4
demand measurement (increments of 1)
in minutes
Power Demand Power Demand Logging Setting 5.5.4
Window: Select type of power Fixed or Slide Fixed 5.5.4
demand window
Interval (m): Select interval for taking power 1 to 60 minutes 15 5.5.4
demand measurement (increments of 1)
in minutes
Event Log Event Log Settings for Pickups, 5.5.4
Enable Contact Inputs, 12.2.1
and Communications
I Pickup: Select I Pickup to be logged No or Yes Yes
V Pickup: Select V Pickup to be logged No or Yes No
Freq Pickup: Select Freq Pickup to be logged No or Yes No
PF Pickup: Select PF Pickup to be logged No or Yes No
Unbal Pickup: Select Unbal Pickup to be logged No or Yes No
SYSALM Pickup: Set system alarm pickup No or Yes No
to be logged
Cin 1: Set Cin 1 event to be logged No or Yes No
Cin 2: Set Cin 2 event to be logged No or Yes No
Cin 3: Set Cin 3 event to be logged No or Yes No
Cin 4: Set Cin 4 event to be logged No or Yes No
Cin 5: Set Cin 5 event to be logged No or Yes No
Cin 6: Set Cin 6 event to be logged No or Yes No
Cin 7: Set Cin 7 event to be logged No or Yes No
Cin 8: Set Cin 8 event to be logged No or Yes No
Comm.: Set Comm event to be logged No or Yes No