IL17569
Page 5-16
Effective June, 2001
Table 5.4 Logging Settings (continued)
Display Setting Description Setpoint Range/ Default Selected Refer to
Value Selection Setting Value Sec. #
Datalogger Datalogger Settings 5.5.4
Mode: Select mode of datalogger to be Cont. or 1-Pass Cont.
8.11
continuous (overwrites) or 1-pass
Trigger: Select trigger type Auto or manual Auto
Interval (s): Select interval of datalogging 1 to 3600 seconds 900
in seconds (increments of 1)
Value 1: Set Value 1 to be logged IA, IB, IC, IX, IR, Iavg, I0, Ia
I1, I2, VA, VB, VC, VX,
Value 2: Set Value 2 to be logged VLNavg, VAB, VBC, VCA, Ib
VLLavg, V0, V1, V2, Freq,
Value 3: Set Value 3 to be logged W, VAR, VA, Dsp PF, App PF, Ic
IA Demand, IB Demand,
Value 4: Set Value 4 to be logged IC Demand, W Demand, Ix
VAR Demand, VA Demand,
Value 5: Set Value 5 to be logged Cin1, Cin2, Cin3, Cin4, Va
Cin5, Cin6, Cin7, Cin8,
Value 6: Set Value 6 to be logged LG1, LG2, LG3, LG4, Vb
LG5, LG6, TG1, TG2,
Value 7: Set Value 7 to be logged TG3, TG4, TG5, TG6, IA Vc
THD, IB THD, IC THD,
Value 8: Set Value 8 to be logged VA THD, VB THD, VC THD, Vx
VAB THD, VBC THD,
VCA THD
Waveform Waveform Capture Settings 5.5.4
Capture 8.10
Records: Select size of the waveform 4x64, 8x32, 16x16 16x16
capture using buffer x cycles (buffer x cycles)
PreTrigger: Select # of cycles of 1 to 15 cycles 2
preTrigger data (increments of 1)
OSC Trigger Select how to trigger waveform Disable, Overwrite, or Lock Overwrite
TRIP2: capture on Trip 2 operation
OSC Trigger Select how to trigger waveform Disable, Overwrite, or Lock Disable
dV/dI: capture on a V or I disturbance
OSC Trigger Select how to trigger waveform Disable, Overwrite, or Lock Overwrite
Logic LG6: capture on a LG6 logic operation
OSC Trigger Select how to trigger waveform Disable, Overwrite, or Lock Overwrite
Cntrl PB: capture on pushbutton operation
OSC Trigger Select how to trigger waveform Disable, Overwrite, or Lock Overwrite
Comm: capture on communication
command