Page 5-43
IL17569
Effective June, 2001
Figure 5-3. Logic Setting Flowchart
Logic Gates 1 All six logic gates contain the same
through 6: settings as shown below.
Function: Set to OR, AND, NOR, NAND, Disable. The
Function setting defines the output of the logic
gates with inputs IN1, IN2, IN3, and IN4. The
default setting is OR.
Setting Group: This setting defines the Setting Group for which
the logic gate programming is active. This
setting is also linked to the System Config
settings, which is where the total number of
settings groups (1 to 4) is programmed.
IN1, IN2, IN3, IN4: These settings define the logic inputs to Logic
Gates 1 through 6. See the settings table and
Section 9.6 for a complete description of the
logic input settings.
Timer Gates 1 All six timer gates contain the same settings as
through 6: shown below.
Setting Group: This setting defines the Setting Group for which
the timer gate programming is active. This
setting is also linked to the System Config
settings, which is where the total number of
settings groups (1 to 4) is programmed.